STP capacity is expressed in KLD, kilolitres per day. One KLD is 1,000 litres. Getting it right matters: an undersized STP fails and smells, an oversized one wastes power and struggles to keep biology healthy at low load.
Step 1: estimate daily water use
For residential buildings, a common planning figure is 135 litres per person per day. Offices, schools and hotels use different amounts, so use measured data whenever you can: water bills, meter readings or tanker records.
Step 2: convert water use to sewage
Not all water becomes sewage; some is used in gardens, evaporates or leaves with people. A common assumption is that about 80% of water supplied returns as sewage.
Step 3: add margin for peaks and growth
Sewage arrives in morning and evening peaks. An equalisation tank absorbs these, but the plant still needs some margin. Occupancy also grows over the first years. Engineers typically round up to the next standard size rather than add large blanket margins.
Worked examples
| Building | Basis | Water per day | Sewage (80%) | Plant size |
|---|---|---|---|---|
| 100 flats | 500 people x 135 L | 67.5 KL | 54 KL | 60 KLD |
| Office, 800 staff | Measured 45 L per person | 36 KL | 29 KL | 30 KLD |
| Hotel, 60 rooms + restaurant | Measured from bills | 45 KL | 36 KL | 40 KLD |
Common mistakes
- Sizing on the developer’s brochure occupancy instead of real use.
- Forgetting kitchen, laundry or swimming pool backwash flows.
- Letting stormwater into the sewer, which can double monsoon flow.
- Ignoring phased occupancy, so the plant runs at a fraction of design load for years. Modular plants solve this.
Use these numbers for budgeting. For the final design, we measure and confirm on site. See STP plants for buildings or request a sizing check.